Operation

Installation and Operation Handbook

2-14

2408 and 2404 Controller

Name Description

AL

Alarm list

1 - - -

Alarm 1 setpoint value

2 - - -

Alarm 2 setpoint value

3 - - -

Alarm 3 setpoint value

4 - - -

Alarm 4 setpoint value

In place of dashes, the last three characters
indicate the alarm type. See alarm types
table:

HY 1

Alarm 1 Hysteresis (display units)

HY 2

Alarm 2 Hysteresis (display units)

HY 3

Alarm 3 Hysteresis (display units)

HY 4

Alarm 4 Hysteresis (display units)

Lb t

Loop Break Time in minutes

diAG

Enable Diagnostic alarms ‘

no’ /

YES’

Alarm types table

-FSL

PV Full scale low alarm

-FSH

PV Full scale high alarm

-dEv

PV Deviation band alarm

-dHi

PV Deviation high alarm

-dLo

PV Deviation low alarm

-LCr

Load Current low alarm

-HCr

Load Current high alarm

-FL2

Input 2 Full Scale low alarm

-FH2

Input 2 Full Scale high alarm

-LOP

Working Output low alarm

-HOP

Working Output high alarm

-LSP

Working Setpoint low alarm

-HSP

Working Setpoint high alarm

4rAt

Rate of change alarm (AL 4 only)

Atun Autotune list
tunE One-shot autotune enable
drA

Adaptive tune enable

drA.t Adaptive tune trigger level in

display units. Range = 1 to 9999

Adc

Automatic Droop Compensation
(PD control only)

Name Description

Pid

PID list

G.SP

If Gain Scheduling has been
enabled (see Chapter 4), this
parameter sets the PV below
which ‘

Pid.1’ is active and above

which ‘

Pid.2’ is active.

SEt

Pid.1’ or ‘Pid.2’ selected

Pb

Proportional Band

(

SEt 1)

(in display units)

ti

Integral Time in secs (

SEt 1)

td

Derivative Time in secs (

SEt 1)

rES

Manual Reset (%)

(

SEt 1)

Hcb

Cutback

High

(

SEt 1)

Lcb

Cutback

Low (

SEt 1)

rEL.C Relative Cool Gain

(

SEt 1)

Pb2

Proportional Band

(

SEt 2)

ti2

Integral Time in secs (

SEt 2)

td2

Derivative Time in secs (

SEt 2)

rES.2 Manual Reset (%)

(

SEt 2)

Hcb2

Cutback

High

(

SEt 2)

Lcb2

Cutback

Low

(

SEt 2)

rEL.2 Relative Cool Gain

(

SEt 2)

The following three parameters are used for
cascade control. If this facility is not being
used, then they can be ignored.

FF.Pb SP, or PV, feedforward propband
FF.tr Feedforward trim %
FF.dv PID feedforward limits ± %

mtr

Motor list - see Table 4-3

tm

Valve travel time in seconds

In.t

Valve inertia time in secs

bAc.t

Valve backlash time in secs

mp.t

Minimum ON time of output pulse

U.br

Valve sensor break strategy