Thermcraft XST-6-0-36-3V User Manual
Page 139
Installation and Operation Handbook
Understanding The Ordering Code
2408 and 2404 Controller
A-5
Part 2: Configuration
continued Digital
input 1
Digital
input 2
Control Power
feedback
Cooling Buttons Program
AM S2
XX XX XX MD XX
The example given in the coding is for 2408 PID controller, 85 to 264 Vac, logic heating,
relay cooling, low alarm relay, high alarm relay, RS485 Modbus comms, PDSIO setpoint
retransmission, type K thermocouple, 0 to 1000
o
C, Auto/manual select, second setpoint
select, manual button disabled.
Digital inputs 1 & 2
XX Disabled
AT
Adaptive tune enable
AM Manual
select
FA Select
full access level
SR Remote
setpoint
select
RB
Simulates UP button
S2 Second
setpoint
select
LB
Simulates DOWN button
EH Integral
hold
SB Simulates
SCROLL
button
AC Alarm
acknowledge PB
Simulates PAGE button
RP
Setpoint rate limit
enable
B1
Least sig. BCD dig.
RN Run
program
B2
2nd BCD digit
HO Hold
program
B3
3rd BCD digit
RE Reset
program
B4
4th BCD digit
RH Run/hold
program
B5
5th BCD digit
KL Keylock
B6
Most sig. BCD digit
NT Run/Reset
program SY
Standby - ALL ops OFF
TN Reset/Run
program SG
Skip segment (without
changing SP)
HB Prog.
holdback
enable
SC
Program synch.
P2 PID2
select
PV Select
PV2
ST
One-shot tune enable
AG
Advance to end of
segment (& step to target
setpoint)
M5
CTX (mode 5)
(input 2 only)
Options
Control action
XX
Reverse acting (standard)
DP
Direct acting PID control
Power feedback
XX
Enabled on logic, relay &
triac heating
PD Feedback
disabled
Cooling options
XX Linear
cooling
CF Fan
cooling
CW Water
cooling
CL Oil
cooling
CO On/off
cooling
Front panel buttons
XX Enabled
MD
Auto/man button disabled
MR
Auto/man & run/hold
disabled
RD
Run/hold button disabled
Programmer time units
XX
Dwell & ramp in minutes
HD
Dwell time in hours
HR
Ramp rate in units/hour