Safety Information

Installation and Operation Handbook

E-4

2408 and 2404 Controller

Controller Configuration and Node Address

Having connected the controller to the network, it must be configured for Profibus
communications and a node address assigned.

Configuration

In the

HA list set Func = ProF.
















Note: The baud rate is automatically selected by the master.

Assigning a Node Address

Refer to the main handbook for instructions on how to select and change parameters.



















HA

ConF

id

CmS

Func

ProF

rEs

FULL

Comms configuration list -

HA

Refer to the main handbook for instructions on how to select configuration level
and access the

HA list

Identity of module
This should be a read-only parameter displaying

Cms

Resolution

FuLL = Full, Int = Integer

This is the only other parameter that appears in this list when

ProF is selected as

the function.

Function
Set

Func = Prof to select Profibus protocol

cmS

LiSt

Addr

1

Stat

run

Comms list
From the HOME display, press

until you reach the

cmS list

Node address
Press

to display the node address. Press

or

to set the desired

address.

0 -126

Comms Status
This is a read-only diagnostic display
rdy Ready

to

run

run Comms

running