Thermcraft XST-6-0-36-3V User Manual
Page 164
Safety Information
Installation and Operation Handbook
E-4
2408 and 2404 Controller
Controller Configuration and Node Address
Having connected the controller to the network, it must be configured for Profibus
communications and a node address assigned.
Configuration
In the
HA list set Func = ProF.
Note: The baud rate is automatically selected by the master.
Assigning a Node Address
Refer to the main handbook for instructions on how to select and change parameters.
HA
ConF
id
CmS
Func
ProF
rEs
FULL
Comms configuration list -
HA
Refer to the main handbook for instructions on how to select configuration level
and access the
HA list
Identity of module
This should be a read-only parameter displaying
Cms
Resolution
FuLL = Full, Int = Integer
This is the only other parameter that appears in this list when
ProF is selected as
the function.
Function
Set
Func = Prof to select Profibus protocol
cmS
LiSt
Addr
1
Stat
run
Comms list
From the HOME display, press
until you reach the
cmS list
Node address
Press
to display the node address. Press
or
to set the desired
address.
0 -126
Comms Status
This is a read-only diagnostic display
rdy Ready
to
run
run Comms
running