Programmer Operation
Installation and Operation Handbook
5-12
2416 Controller
Segment type
Select the segment type using
or
:
•
rmP.r
Ramp to a new setpoint at a set rate
•
rmP.t
Ramp to a new setpoint in a set time
•
dwEl
Dwell for a set time
•
StEP
Step to a new setpoint
•
cALL
Call another program as a subroutine
(only available in 4-program controllers)
•
End
Make this segment end of program.
Press
The parameters that follow ‘
tYPE’ depend on the type of segment selected.
Parameter
Segment type selected
rmP.r rmP.t dwEl StEP cALL
End
Hb
9
9
9
9
tGt
9
9
9
rAtE
9
dur
9
9
PrG.n
9
outn
9
9
9
9
9
cYc.n
9
dwEl
9
End.t
9
Pwr
9
Table 5-3 Parameters that follow segment
tYPE
Holdback type
[Only appears when Holdback per segment has been selected.]
Use
or
to select:
•
OFF
: Holdback disabled
•
Lo
:
Deviation Low Holdback
•
Hi
:
Deviation High Holdback
•
bAnd
:
Deviation Band Holdback
Press
Target setpoint
Target setpoint for ‘
rmP.r’, ‘rmP.t’ or ‘StEP’ segments.
Set the target setpoint using
or
.
Press
Continued on the next page.
Hb
bAnd
tgt
100
type
rmp.r