Thermcraft XST-6-0-36-3V User Manual
Page 41
Installation and Operation Handbook
Installation
2408 and 2404 Controller
1-9
Four terminal modules
Note: Module 1 is connected to terminals 1A, 1B, 1C and 1D
Module 2 is connected to terminals 2A, 2B, 2C and 2D
Module 3 is connected to terminals 3A, 3B, 3C and 3D
Module type
Terminal identity
Possible functions
A
B
C
D
Relay: changeover
(2A, 264 Vac max.)
Heating, cooling,
alarm, or program
event output
DC control: Isolated
(10V, 20mA max.)
+
−
Heating,
or
cooling
24Vdc transmitter
supply
*
+
−
To power process
inputs
Potentiometer input
100
Ω to 15KΩ
*
+0.5Vdc
0V
Motorised Valve
Position feedback
DC retransmission
+
−
Retrans. of setpoint,
or process value
DC remote input or
Process Value 2
(Module 3 only)
0-10Vdc RT
source ±100mV
0-20mA
COM
Remote Setpoint
Second PV
Dual output modules
Dual relay
(2A, 264 Vac max.)
Heating + cooling
Dual alarms
Valve raise &
lower
Dual Triac
(1A, 30 to 264Vac)
Heating
+
cooling
Valve raise &
lower
Dual logic + relay
(Logic is non-isolated)
+
−
Heating
+
cooling
Dual Logic + triac
(Logic is non-isolated)
+
−
Heating
+
cooling
Triple logic input and output modules - see ratings on the next page
Triple contact input
Input 1
Input 2
Input 3
Common
Triple logic input
Input 1
Input 2
Input 3
Common
Triple logic output
Output 1
Output 2
Output 3 Common
Program events
* Can be ordered fitted in module positions 2 & 3 only.
N/C
N/O
Line
Load
Line
Load
Line
Load