Load Current Monitoring and Diagnostics Installation and Operation Handbook
D-10 2408 and 2404 Controller
TO CONFIGURE LOW AND HIGH CURRENT TRIP ALARMS
Alarm 1 will be configured as Load Current Low (
Lcr)
Alarm 2 will be configured as Load Current High (
Hcr)
Do This
This Is The Display You Should See
Additional Notes
Press
button
until the
AL Conf
is displayed
This opens the
configuration list
which contains the
Alarms
Press
to show
AL1 (alarm 1)
Press
or
to show
LCr
Press
until
AL2 (alarm 2)
appears
Press
or
to show
HCr
To select alarm 1
To make alarm 1 =
Low Current
To select alarm 2.
To make alarm 2 =
High Current
Note:- The above alarms are known as SOFT ALARMS because they are indication
only.
AL
Conf
AL1
LCr
After 0.5 sec the
display will blink to
show the alarm type
has been accepted
AL2
HCr
After 0.5 sec the
display will blink to
show the alarm type
has been accepted