Cal.s, None, User – Thermcraft XST-6-0-36-3V User Manual
Page 132

User Calibration
Installation and Operation Handbook
7-6
2408 and 2404 Controller
Select Low-point Calibration
This is the Calibration Status display. This display shows that
no input is selected for calibration.
• nonE: No
selection
• ip1.L:
Input 1 (PV1) calibration low-point selected
• ip1.H:
Input 1 (PV1) calibration high-point selected
• ip2.L:
Input 2 (PV2) calibration low-point selected
• ip2.H:
Input 2 (PV2) calibration high-point selected
Use
/
to select the parameter for the Low Calibration
point of Input 1, ‘
ip1.L’.
Press
Adjust low-point calibration
This is the display for adjusting the Low Calibration point of
Input 1. The lower readout is a live reading of the process
value, which changes as the input changes.
Make sure that the calibration source is connected to the
terminals of Input 1, switched on and feeding a signal to the
controller. It should be set to the desired low-point calibration
value. If the lower readout does not show this value, then use
/
to adjust the reading to the required value.
Press
to return to the ‘
ip-List’ header.
To perform the High-point Calibration, repeat the above
procedure, selecting ‘
ip1.H’ in the ‘CAL.S’ display for
adjustment.
Press
three times.
Calibration type
‘
USEr’ was selected for the Low-point Calibration, and has
remained selected.
Press
CAL.S
nonE
CAL
USEr
Adj
25
x 3