beautypg.com

Thermcraft XST-6-0-36-3V User Manual

Page 118

background image

Configuration

Installation and Operation Handbook

6-18

2408 and 2404 Controller

Name

Description

Values Meaning

For ‘

id’ = ‘dC.OP’, ‘dc.rE’, or ‘dc.OP’ use this parameter table:

Func

Function

nonE Function disabled

HEAt Heating output

COOL Cooling output

PV

Retransmission of PV

wSP

Retransmission of setpoint

Err

Retransmission of error signal

OP

Retransmission of OP power

VAL.L

% PID, or Retrans’n Value,
giving minimum output

VAL.H

% PID, or Retrans’n Value,
giving maximum output

unit

voLt = Volts, mA = milliamps

Out.L

Minimum electrical output

Out.H

Maximum electrical output

For ‘

id’ = ‘LoG.i’ (i.e logic input) use the

LA Conf’ list on Page 6-13.


2A/b/C

Module 2 configuration

As per module 1 configuration, but excluding the ‘

SSr.1’, ‘SSr.2’ functions.

id

Identity of module installed.

As per module 2 plus:

tPSU

Transmitter power supply

Pot.i

Potentiometer input

For ‘

id’ = ‘Pot.i (i.e. potentiometer input module) use this parameter table:

Func

Function

nonE

Function disabled

rSP

Remote Setpoint

Fwd.i

Feedforward input

rOP.h

Remote OP power max.

rOP.L

Remote OP power min.

VPoS

Motorised valve position

VAL.L

Displayed value low
equivalent to 0%
potentiometer position

VAL.H

Displayed value high
equivalent to 100%
potentiometer position

VAL.L

Out.H

Out.L

VAL.H

Electrical
Output

%PID, or Retransmission Value

VAL.L

100%

0%

VAL.H

Displayed value

Potentiometer
position

This manual is related to the following products: