Installation and Operation Handbook

Configuration

2408 and 2404 Controller

6-11

AL

Alarm configuration

Values

The controller contains four ‘soft’ alarms, which are
configured in this list. Once configured, they can be
attached to a physical output as described in the alarm
relay configuration list,

AA Conf’.

AL1 Alarm 1 Type

see Table A

Ltch Latching

no/YES/Evnt/mAn

*

bLoc Blocking

no/YES

AL2 Alarm 2 Type

see Table A

Ltch Latching

no/YES/Evnt/mAn

*

bLoc Blocking

no/YES

AL3 Alarm 3 Type

see Table A

Ltch Latching

no/YES/Evnt/mAn

*

bLoc Blocking

no/YES

AL4 Alarm 4 Type

see Table A

Ltch Latching

no/YES/Evnt/mAn

*

bLoc Blocking

(not if ‘

AL4’ = ‘rAt’)

no/YES

Sbr.t Sensor break trip alarm

latching type.
Disable = process alarms
inhibited when in sensor
break
Enable = process alarms
shown when in sensor
break

En Enable
Dis Disable

*

Alarm Modes

no’ means that the alarm will be non-latching.

YES’ means that the alarm will be latched, with automatic

resetting. Automatic resetting means that if a reset is actioned
before the alarm has cleared, then it will automatically reset
when it clears.

Evnt’ means that the alarm is used to trip an external event. If

this option is selected the front panel alarm message will not
appear.

mAn’ means that the alarm will be latched, and can only be

reset after it has first cleared (called ‘manual reset mode’).

Table A - Alarm types
Value Alarm type
OFF No alarm

FSL PV Full scale low

FSH PV Full scale high

dEv PV Deviation band

dHi PV Deviation high

dLo PV Deviation low

LCr Load Current low

HCr Load Current high

FL2 Input 2 Full Scale low

FH2 Input 2 Full Scale

high

LOP Working Output low

HOP Working Output high

LSP Working Setpoint low

HSP Working Setpoint high

rAt PV Rate of change

AL4 only

Ct.OP CT open circuit
Ct.Sh CT short circuit