Configuration
Installation and Operation Handbook
6-16
2408 and 2404 Controller
Name Description
Values
Meaning
For ‘
id’ = ‘Pdsi’ (PDS setpoint input) use this parameter table:
Func
Function
SP.iP
PDS setpoint input
VAL.L
Setpoint Displayed Value - Low
VAL.H
Setpoint Displayed Value - High
Note:
Having configured the module function as remote setpoint you must then specify the type of
remote setpoint in the SP-conf list
JA
Comms 2 module config
Same as HA but is only available as PDS.
VAL.L
100%
0%
VAL.H
Displayed Value
Electrical Input