Thermcraft XST-6-0-36-3V User Manual
Page 74
Access Levels
Installation and Operation Handbook
3-4
2408 and 2404 Controller
EDIT LEVEL
Edit level is used to set which parameters you can view and adjust in Operator level. It also
gives access to the ‘Promote’ feature, which allows you to select and add (‘Promote’) up to
twelve parameters into the Home display list, thereby giving simple access to commonly used
parameters.
Setting operator access to a parameter
First you must select
Edit level, as shown on the previous page.
Once in
Edit level, you select a list, or a parameter within a list, in the same way as you
would in Operator, or Full, level
− that is to say, you move from list header to list header by
pressing
, and from parameter to parameter within each list using
.
However, in Edit level what is displayed is not the value of a selected parameter, but a code
representing that parameter’s availability in Operator level.
When you have selected the required parameter, use
and
buttons to set its availability
in Operator level.
There are four codes:
ALtr Makes a parameter alterable in Operator level.
PrO
Promotes a parameter into the Home display list.
rEAd Makes a parameter, or list header, read-only (it can be viewed but not altered).
HIdE Hides a parameter, or list header.
For example:
Hiding or revealing a complete list
To hide a complete list of parameters, all you have to do is hide the list header. If a list
header is selected, only two selections are available:
rEAd and HIdE.
(It is not possible to hide the ‘
ACCS’ list, which always displays the code: ‘LiSt’.)
Promoting a parameter
Scroll through the lists to the required parameter and choose the ‘
PrO’ code. The parameter
is then automatically added (promoted) into the Home display list. (The parameter will also
be accessible, as normal, from the standard lists.) A maximum of twelve parameters can be
promoted. Promoted parameters are automatically ‘alterable’.
Please note, in the ‘
PrOG List’, the parameters from segment number (SEG.n) onwards
cannot be promoted.
The parameter selected is Alarm 2, Full Scale Low
It will be alterable in Operator level