beautypg.com

Thermcraft XST-6-0-36-3V User Manual

Page 74

background image

Access Levels

Installation and Operation Handbook

3-4

2408 and 2404 Controller

EDIT LEVEL

Edit level is used to set which parameters you can view and adjust in Operator level. It also
gives access to the ‘Promote’ feature, which allows you to select and add (‘Promote’) up to
twelve parameters into the Home display list, thereby giving simple access to commonly used
parameters.

Setting operator access to a parameter
First you must select

Edit level, as shown on the previous page.

Once in

Edit level, you select a list, or a parameter within a list, in the same way as you

would in Operator, or Full, level

− that is to say, you move from list header to list header by

pressing

, and from parameter to parameter within each list using

.

However, in Edit level what is displayed is not the value of a selected parameter, but a code
representing that parameter’s availability in Operator level.

When you have selected the required parameter, use

and

buttons to set its availability

in Operator level.
There are four codes:
ALtr Makes a parameter alterable in Operator level.

PrO

Promotes a parameter into the Home display list.

rEAd Makes a parameter, or list header, read-only (it can be viewed but not altered).

HIdE Hides a parameter, or list header.


For example:

Hiding or revealing a complete list
To hide a complete list of parameters, all you have to do is hide the list header. If a list
header is selected, only two selections are available:

rEAd and HIdE.

(It is not possible to hide the ‘

ACCS’ list, which always displays the code: ‘LiSt’.)

Promoting a parameter
Scroll through the lists to the required parameter and choose the ‘

PrO’ code. The parameter

is then automatically added (promoted) into the Home display list. (The parameter will also
be accessible, as normal, from the standard lists.) A maximum of twelve parameters can be
promoted. Promoted parameters are automatically ‘alterable’.

Please note, in the ‘

PrOG List’, the parameters from segment number (SEG.n) onwards

cannot be promoted.

The parameter selected is Alarm 2, Full Scale Low

It will be alterable in Operator level

This manual is related to the following products: