Load Current Monitoring and Diagnostics Installation and Operation Handbook

D-6 2408 and 2404 Controller

TO SET THE ALARM TRIP LEVELS

Do This

This Is The Display You Should See

Additional Notes

From the HOME
display

press

until the

AL LiSt is

displayed

Press

button

until the desired
alarm number is
displayed

Press

or

to

adjust the alarm trip
level

To select the Alarm
List header

To select the
diagnostic alarm
parameter found
under the Alarm List
header

The alarm trip level
is set to 123

SHORT CIRCUIT SSR ALARM AND HEATER FAIL ALARM

These alarms exist as Diagnostic Alarms in the controller. To make the alarm active it is
only necessary to turn on the diagnostic alarm feature in the Alarm List in the Operator Level

Do This

This Is The Display You Should See

Reason

From the HOME
display press

button until the

AL

LiSt is displayed



Press

until

DiAG is displayed



Press

or

to select

YES
















This opens the list
which contains the
diAG mnemonic




This activates the
diAG mnemonic to

allow Diagnostic
Alarms to be
displayed in the
lower readout of the
HOME display

RELAY OUTPUTS

The fixed relay output connected to terminals AA to AC in a 1/8 or 1/4 DIN controller is
normally used for alarm purposes. In addition, any plug in module can be used for alarms
provided they are not already being used for another purpose , such as control. Any one or
more alarms can be attached to an output, which will operate when an alarm occurs. Contacts
are rated at 2A 264Vac for operating external beacons or audible devices.

AL

LiSt

DiAG

YES

AL

LiSt

1---

123

1 2 3 or 4

indicates the alarm
number;
--- indicates the

alarm type:-
e.g.

LCr or HCr