Thermcraft XST-6-0-36-3V User Manual
Page 265
Installation and Operation Handbook
Load Current Monitoring and Diagnostics
2416 Controller
8-9
8.9
TO ATTACH SOFT ALARMS TO A RELAY OUTPUT
Any one alarm indicated above may be attached to an output (normally a relay). Alternatively
any combination of alarms may be attached to operate a relay using the procedure below:-
Do This
This Is The Display You Should See
Additional Notes
Press “PAGE” key
as many times
as necessary to
3A
ConF
Any output module
can be configured
for an alarm output
provided it is not
used for any other
purpose, eg as a
control output.
In place of
3A you
should select the
module required, i.e.
1A or 2A
Press
until
1--- is displayed
Press
or
to select
YES or
Repeat the above
step for every alarm
to be attached to the
output
1---- denotes alarm 1
followed by three letters
which denote the alarm
type e.g.
LCr
yes means that the
selected output will
activate when an
alarm occurs in
normal operation
no means the
output will not
activate
3A
Conf
1---
yes
Alarms Connected to a
Relay Output
dIG
SEnS
nor
inv
Output
Module
Soft
Alarms
OR
3A