beautypg.com

Thermcraft XST-6-0-36-3V User Manual

Page 65

background image

Operation

Installation and Operation Handbook

2408 and 2404 Controller

2-15

Name Description

SP

Setpoint list

SSEL Select

SP 1 to SP16, depending

on configuration

L-r Local

(

Loc) or remote (rmt)

setpoint select

SP 1

Setpoint one value

SP 2

Setpoint two value

rm.SP

Remote setpoint value

rmt.t

Remote setpoint trim

rat

Ratio setpoint

Loc.t

Local setpoint trim

SP L

Setpoint 1 low limit

SP H Setpoint 1 high limit
SP2.L

Setpoint 2 low limit

SP2.H

Setpoint 2 high limit

SPrr

Setpoint Rate Limit

Hb.ty

Holdback Type for setpoint rate
limit (

OFF, Lo, Hi, or bAnd)

Hb

Holdback Value for setpoint rate
limit in display units. (

Hb.ty ≠

Off)

iP

Input list

FiLt

IP1 filter time constant (0.0 -
999.9 seconds).

FLt.2

IP2 filter time constant (0.0 -
999.9 seconds).

Hi.IP
Lo.Ip

Transition of control between
ip.1 and ip.2. (if configured)

The transition region is set by the
values of ‘

Lo.Ip’ and ‘Hi.Ip’.

PV =

ip.1 below ‘Lo.Ip’

PV =

ip.2 above ‘Hi.Ip’

F.1
F.2

Derived function, (if configured)
PV = (

f.1 x iP1) + (f.2 x iP2).

F.1’ and ‘F.2’ are scalars with the

range -9.99 to 10.00

PV.ip Selects

ip.1’ or ‘ip.2’

Continued in next column

Name Description

iP

Input list - continued

The next 3 parameters appear if User
Calibration has been enabled. (Refer to
Chapter 7.) By default they are hidden
when in Operator level. To prevent
unauthorised adjustment, we recommend
that they are only made available in

FuLL

access level.
CAL

FACt’ - reinstates the factory

calibration and disables User
calibration. Next 2 parameters
will not appear.

USEr’ - reinstates any previously

set User calibration. All
parameters below now appear.

CAL.s

Selected calibration point

nonE’, ’iP1.L’, ‘ip1.H’, ’iP2.L’,

ip2.H’

AdJ *

User calibration adjust, if

CAL.s =

iP1.L’, ‘ip1.H’, ’iP2.L’, ‘ip2.H’

OFS.1

IP1 calibration offset

OFS.2

IP2 calibration offset

mV.1

IP1 measured value (at terminals)

mV.2

IP2 measured value (at
terminals), if DC input in Module 3
position

CJC.1

IP1 cold junction temp. reading

CJC.2

IP2 cold junction temp. reading

Li.1

IP1 linearised value

Li.2

IP2 linearised value

PV.SL

Shows the currently selected PV
input - ‘

ip.1’ or ‘ip.2’

* Do not make adjustments using the

AdJ

parameter unless you wish to change the
controller calibration.

This manual is related to the following products: