2408 and 2404 Controller
Profibus-DP is a multimaster, master-slave, token passing network. The 2408f and the 2404f
operate as intelligent slave units. More detailed information, including a detailed guide to
products available, may be obtained from the various world wide Profibus user organisations.
You will find contact information in trade magazines or by reference to
http://www.profibus.com on the World Wide Web.
Technical Specification
Physical Medium
2-wire RS485
Network topology
Linear bus with active termination of the bus at both ends
Stub lines permitted if < 6.6m in length
Protocol
Profibus-DP,
intelligent
slave
Baud rate
Up to 1.5Mb/s
Number of stations
32 per network segment. Up to 127 with repeaters
Electrical Connections
The diagram below is also shown in Chapter 1.
SHIELD
Station 1
HA
HB
HC
HD
HE
HF
Shield
VP (+5Vdc Voltage Potential)
B (Rx/Tx +ve)
A (Rx/Tx -ve)
DGND (Digital ground)
Not connected
B
390
Ω
Last Station
HA
HB
HC
HD
HE
HF
Shield
VP (+5Vdc Voltage Potential)
B (Rx/Tx +ve)
A (Rx/Tx -ve)
DGND (Digital ground)
Not connected
Intermediate stations
Last station only requires
terminating resistors
390
Ω
220
Ω
A
B
A
B
A
2408f or 2404f controller
2408f or 2404f controller
Twisted
pair
Twisted
pair