Thermcraft XST-6-0-36-3V User Manual
Page 112
Configuration
Installation and Operation Handbook
6-12
2408 and 2404 Controller
The following parameters apply if the standard 8-segment programmer is to be configured.
PROG Programmer configuration Values
Meaning
PtyP Programmer type
nonE
Programmer disabled (
factory setting
)
1
8-segment programmer enabled
HbAc Holdback
SEG
ProG
Holdback is individually selectable in
each segment.
Holdback is applied across the whole
Program.
Pwr.F Power fail recovery
cont
Continue from last setpoint (SP)
rmP.b
Ramp from PV to SP at last ramp rate
rSEt
Reset the program
Srvo Starting setpoint of a
to.PV
From the Process Value (PV)
program (Servo point)
to.SP
From the setpoint
The following parameters apply if a 16-segment programmer is to be configured.
PROG Programmer configuration Values
Meaning
PtyP Programmer type
nonE
Programmer disabled
1
Single program
4
Four programs
20
Twenty programs
HbAc Holdback
SEG
ProG
Holdback is individually selectable in
each segment.
Holdback is applied across the whole
Program.
Pwr.F Power fail recovery
cont
Continue from last setpoint (SP)
rmP.b
Ramp from PV to SP at last ramp rate
rSEt
Reset the program
Srvo Starting setpoint of a
to.PV
From the Process Value (PV)
program (Servo point)
to.SP
From the setpoint
out
Programmable event
outputs
no
YES
Disabled
Enabled
SYNC Synchronisation of programs
of several programmers
no
YES
Disabled
Enabled