Configuration

Installation and Operation Handbook

6-16

2416 Controller





Name

Description

Values

Meaning

DC Output Calibration

The following parameters apply to DC output modules ie for

rcAL

=

1A.Hi

to

3A.Lo

cAL.H

Output Calibration High

0

0 = Factory set calibration.
Trim value until output = 9V, or
18mA

cAL.L

Output Calibration Low

0

0 = Factory set calibration.
Trim value until output = 1V, or 2mA


User calibration

UCAL

User calibration enable

Yes/no

pt1.L

Low calibration point for Input
1

The factory calibration point at which the low point
offset was performed.

pt1.H

High calibration point for
Input 1

The factory calibration point at which the high point
offset was performed.

OF1.L

Offset Low for Input 1

Calculated offset, in display units.

OF1.H

Offset High for Input 1

Calculated offset, in display units.



Name

Description

Values

Meaning

PASS

Password configuration

ACC.P

Full or Edit level password

cnF.P

Configuration level
password

Note:- When passwords are changed please make a note of the new numbers


Exit

Exit configuration

no/YES