Thermcraft XST-6-0-36-3V User Manual
Page 248
Configuration
Installation and Operation Handbook
6-16
2416 Controller
Name
Description
Values
Meaning
DC Output Calibration
The following parameters apply to DC output modules ie for
rcAL
=
1A.Hi
to
3A.Lo
cAL.H
Output Calibration High
0
0 = Factory set calibration.
Trim value until output = 9V, or
18mA
cAL.L
Output Calibration Low
0
0 = Factory set calibration.
Trim value until output = 1V, or 2mA
User calibration
UCAL
User calibration enable
Yes/no
pt1.L
Low calibration point for Input
1
The factory calibration point at which the low point
offset was performed.
pt1.H
High calibration point for
Input 1
The factory calibration point at which the high point
offset was performed.
OF1.L
Offset Low for Input 1
Calculated offset, in display units.
OF1.H
Offset High for Input 1
Calculated offset, in display units.
Name
Description
Values
Meaning
PASS
Password configuration
ACC.P
Full or Edit level password
cnF.P
Configuration level
password
Note:- When passwords are changed please make a note of the new numbers
Exit
Exit configuration
no/YES