Programmer Operation
Installation and Operation Handbook
5-8
2408 and 2404 Controller
CONFIGURING THE PROGRAMMER
When first installing a programmer you should check that the configuration conforms to your
requirement.
Configuration defines:
• the number of stored programs
(multi-programmer only)
• the holdback strategy
• the power fail strategy
• the servo type
• if event outputs are available
(not 8-segment programmer)
• if program synchronisation is available.
(not 8-segment programmer)
• selection of program number using digital inputs (multi-programmer only)
To check, or change, the configuration, select Configuration level. See Chapter 6.
Programmer list header
After selecting Configuration mode, press
until the
PROG
ConF header is displayed.
Press
Number of programs
Use
or
to select:
•
nonE
: Disable built-in 8-segment programmer
•
1
:
Enable built-in 8-segment programmer
For 16-segment programmers:
•
nonE
: no programs
•
1
:
One stored program
•
4
:
Four stored programs
•
20: Twenty stored programs
Press
Holdback Strategy
Use
or
to select:
•
SEG
:
Holdback type to be set in each segment
•
ProG
:
Holdback type to be set for the whole program
Press
Continued on the next page.