Configuration

Installation and Operation Handbook

6-6

2416 Controller

6.6

CONFIGURATION PARAMETER TABLES

Name

Description

Values

Meaning

inSt

Instrument configuration

CtrL

Control type

Pid

PID control

On.OF

On/off control

VP

Boundless motorised valve
control - no feedback required

Act

Control action

rEv

Reverse acting

dir

Direct acting

CooL

Type of cooling

Lin

Linear

oiL

Oil (50mS minimum on-time)

H2O

Water (non-linear)

FAn

Fan (0.5S minimum on-time)

on.OF

On/off cooling

ti.td

Integral & derivative

SEc

Seconds, OFF to 9999

time units

min

Minutes, OFF to 999.9

dtYP

Derivative type

PV

Err

Operates on rate of change of
PV
Operates on rate of change of
error

m-A

Front panel Auto/Man button

EnAb

Enabled

diSA

Disabled

r-h

Front panel Run/Hold button

EnAb

Enabled

diSA

Disabled

PwrF

Power feedback

on

On

OFF

Off

Fwd.t

Feed forward type

none

None

FEEd

Normal feed forward

SP.FF

Setpoint feed forward

PV.FF

PV feed forward

Pd.tr

Manual/Auto transfer when

no

Non-bumpless transfer

using PD control

YES

Bumpless transfer - (Pre-loads
Manual Reset value)

Sbr.t

Sensor break output

Sb.OP

Go to pre-set value

HoLd

Freeze output

FOP

Forced manual output

no

Bumpless Auto/Manual transfer

trac

Returns to the Manual value
that was set when last in
Manual mode

Step

Steps to forced output level.
Value set in ‘

FOP’ of ‘op-List’

in Operator Level

bcd

BCD input function

nonE

Not used

ProG

SP

Only functional in Models 2408
& 2404. Set ‘

bcd

’ to ‘

none

Select setpoint number

Gsch

Gain Schedule Enable

no

Disabled

YES

Enabled