Thermcraft XST-6-0-36-3V User Manual
Page 238
Configuration
Installation and Operation Handbook
6-6
2416 Controller
6.6
CONFIGURATION PARAMETER TABLES
Name
Description
Values
Meaning
inSt
Instrument configuration
CtrL
Control type
Pid
PID control
On.OF
On/off control
VP
Boundless motorised valve
control - no feedback required
Act
Control action
rEv
Reverse acting
dir
Direct acting
CooL
Type of cooling
Lin
Linear
oiL
Oil (50mS minimum on-time)
H2O
Water (non-linear)
FAn
Fan (0.5S minimum on-time)
on.OF
On/off cooling
ti.td
Integral & derivative
SEc
Seconds, OFF to 9999
time units
min
Minutes, OFF to 999.9
dtYP
Derivative type
PV
Err
Operates on rate of change of
PV
Operates on rate of change of
error
m-A
Front panel Auto/Man button
EnAb
Enabled
diSA
Disabled
r-h
Front panel Run/Hold button
EnAb
Enabled
diSA
Disabled
PwrF
Power feedback
on
On
OFF
Off
Fwd.t
Feed forward type
none
None
FEEd
Normal feed forward
SP.FF
Setpoint feed forward
PV.FF
PV feed forward
Pd.tr
Manual/Auto transfer when
no
Non-bumpless transfer
using PD control
YES
Bumpless transfer - (Pre-loads
Manual Reset value)
Sbr.t
Sensor break output
Sb.OP
Go to pre-set value
HoLd
Freeze output
FOP
Forced manual output
no
Bumpless Auto/Manual transfer
trac
Returns to the Manual value
that was set when last in
Manual mode
Step
Steps to forced output level.
Value set in ‘
FOP’ of ‘op-List’
in Operator Level
bcd
BCD input function
nonE
Not used
ProG
SP
Only functional in Models 2408
& 2404. Set ‘
bcd
’ to ‘
none
Select setpoint number
Gsch
Gain Schedule Enable
no
Disabled
YES
Enabled