Configuration

Installation and Operation Handbook

6-22

2408 and 2404 Controller

DC Output Calibration

The following parameters apply to DC output modules ie for

rcAL

=

1A.Hi

to

3A.Lo

cAL.H

Output Calibration High

0 0 = Factory set calibration.

Trim value until output = 9V, or
18mA

cAL.L

Output Calibration Low

0 0 = Factory set calibration.

Trim value until output = 1V, or
2mA


User calibration

UCAL

User calibration enable

Yes/no

pt1.L

Low calibration point for Input 1

The factory calibration point at which the low
point offset was performed.

pt1.H

High calibration point for Input 1

The factory calibration point at which the high
point offset was performed.

OF1.L

Offset Low for Input 1

Calculated offset, in display units.

OF1.H

Offset High for Input 1

Calculated offset, in display units.

pt2.L

Low calibration point for Input 2

The factory calibration point at which the low
point offset was performed.

pt2.H

High calibration point for Input 2

The factory calibration point at which the high
point offset was performed.

OF2.L

Offset Low for Input 2

Calculated offset, in display units.

OF2.H

Offset High for Input 2

Calculated offset, in display units.



Name

Description

Values

Meaning

PASS

Password configuration

ACC.P

FuLL or Edit level password

cnF.P

Configuration level
password

Note:- When passwords are changed please make a note of the new numbers

Exit

Exit configuration

no/YES