2416 Controller
no.io
No I/O
None of the expected I/O
modules is fitted.
This error message normally occurs when pre-
configuring a controller without installing any of
the required I/O modules.
rmt.F
Remote input failure.
Either the PDSIO input, or
the remote DC input, is
open or short circuit
Check for open, or short circuit wiring on the
PDSIO, or remote DC, input.
LLLL
Out of range low reading
Check the value of the input.
HHHH
Out of range high reading
Check the value of the input.
Err1
Error 1: ROM self-test fail
Return the controller for repair.
Err2
Error 2: RAM self-test fail
Return the controller for repair.
Err3
Error 3: Watchdog fail
Return the controller for repair.
Err4
Error 4: Keyboard failure
Stuck button, or a button
was pressed during power
up.
Switch the power off and then on, without
touching any of the controller buttons.
Err5
Error 5: Faulty internal
communications.
Check printed circuit board interconnections. If
the fault cannot be cleared, return the controller
for repair.
Err6
Digital filter chip faulty or
loose board inside
controller
Return the controller for repair.
Err7
PV id failure/PSU failure
Return the controller for repair.
Err8
Module 1 id error
Faulty or loose module or may be isolation
problem
Err9
Module 2 id error
Faulty or loose module or may be isolation
problem
ErrA
Module 3 id error
Faulty or loose module or may be isolation
problem
DCF
DC output fail
Return the controller for repair
Tu.Er
Tune error – shown If any
one stage of the auto-
tuning process exceeds
two hours
Check response time of process: check that the
sensor has not failed: check that the loop is not
broken. Acknowledge by pressing ‘page’ key
and ‘scroll’ key together
P.br
Potentiometer break
Check that the feedback potentiometer is
correctly connected or the pot is not open circuit
Table 2-2b Diagnostic alarms