Connecting Your Ultra5000
Wiring Power Connections
Power wiring requirements are given in the table below.
For additional information refer to the
section in Appendix A. Refer to Appendix B for the power wiring
diagram for your Ultra5000 drive.
The internal 5V dc power supply fuse opens at 3 amps and
automatically resets itself when the current falls below 3 amps. There
are no internal fuses requiring replacement.
The Ultra5000 utilizes solid state motor overload protection which
operates in accordance with UL 508C.
IMPORTANT
Ultra5000 Drives:
Provide this
input power:
1
With this type
of wire:
Phasing of main
AC power:
Earth ground
connection:
Terminal block
torque values:
2098-IPD-005
xx, -010-xx, and -02-xx
100-240V ac
single phase
Copper with 75
°
C (194
° F)
minimum rating
Arbitrary
Required
(for safe and
proper system
operation)
1.25 Nm (11
lb-in.)
2098-IPD-030
-xx
2098-IPD-075
-xx
100-240V ac
3-phase
2098-IPD-150
-xx
2.26 Nm (20
lb-in.)
2098-IPD-HV
xxx-xx
207-528V ac
3-phase
1.25 Nm (11
lb-in.)
1
The input power may be optionally isolated through a transformer.
Motor overload protection trips:
At:
Eventually
100% overload.
Within 8 minutes
200% overload.
Within 20 seconds
600% overload.