beautypg.com

Wiring power connections, Wiring power connections -14, Refer to wiring – Rockwell Automation 2098-IPD-xxx Ultra5000 Intelligent Positioning Drives Installation Manual User Manual

Page 74: Minal blocks, Refer, Inal blocks, Refer to wiring power connections on

background image

Publication 2098-IN001E-EN-P — April 2002

3-14

Connecting Your Ultra5000

Wiring Power Connections

Power wiring requirements are given in the table below.

For additional information refer to the

General Power Specifications

section in Appendix A. Refer to Appendix B for the power wiring
diagram for your Ultra5000 drive.

The internal 5V dc power supply fuse opens at 3 amps and
automatically resets itself when the current falls below 3 amps. There
are no internal fuses requiring replacement.

The Ultra5000 utilizes solid state motor overload protection which
operates in accordance with UL 508C.

IMPORTANT

The 2098-IPD-HVxxx-xx drives can be powered with
230-240 Vrms in order to be used in conjunction with
motors designed for 230V operation. In such cases,
the voltage levels used for shunting and DC bus
overvoltage limits are adjusted to be compatible with
the voltage limit of the motor.

Ultra5000 Drives:

Provide this

input power:

1

With this type

of wire:

Phasing of main

AC power:

Earth ground

connection:

Terminal block

torque values:

2098-IPD-005

xx, -010-xx, and -02-xx

100-240V ac

single phase

Copper with 75

°

C (194

° F)

minimum rating

Arbitrary

Required

(for safe and
proper system
operation)

1.25 Nm (11
lb-in.)

2098-IPD-030

-xx

2098-IPD-075

-xx

100-240V ac

3-phase

2098-IPD-150

-xx

2.26 Nm (20
lb-in.)

2098-IPD-HV

xxx-xx

207-528V ac

3-phase

1.25 Nm (11
lb-in.)

1

The input power may be optionally isolated through a transformer.

Motor overload protection trips:

At:

Eventually

100% overload.

Within 8 minutes

200% overload.

Within 20 seconds

600% overload.