Connecting Your Ultra5000

3-7

Grounding Multiple Subpanels

To ground multiple subpanels, refer to the figure below.

Figure 3.5

Subpanels Connected to a Single Ground Point

Motor Power Cable Shield Termination

Factory supplied motor power cables for F-Series, H-Series, MP-Series,
N-Series, and W-Series motors are shielded, and the power cable is
designed to be terminated at the drive during installation. A small
portion of the cable jacket is removed which exposes the shield braid.
The exposed area must be clamped to the bottom of the drive chassis
(refer to

Figure 3.6

) using the clamp provided.

Always follow NEC and

applicable local codes

Ground grid or

power distribution

ground

ATTENTION

!

High voltage can be present on the shield of a power
cable if the shield is not grounded.

To avoid hazard of electrical shock, ensure shielded
power cables are grounded at a minimum of one
point for safety.

Failure to observe these safety procedures could
result in personal injury or equipment damage.