Digital inputs, Digital inputs -20 – Rockwell Automation 2098-IPD-xxx Ultra5000 Intelligent Positioning Drives Installation Manual User Manual
Page 46
![background image](/manuals/580388/46/background.png)
Publication 2098-IN001E-EN-P — April 2002
2-20
Ultra5000 Connector Information
Digital Inputs
There are sixteen general purpose digital inputs. They are not
connected in hardware to perform a particular function. All digital
inputs have the same hardware configuration, shown in
.
Inputs 1 and 2 use high-speed circuitry, with minimal propagation
delays, suitable for use in registration applications. Any input can be
assigned through firmware to latch the motor or auxiliary position in
hardware.
Figure 2.8
Digital Input Circuit
The following table provides a description of the digital input
specifications.
IMPORTANT
Configure your digital inputs, in a group, as active
high (current sinking) or active low (current
sourcing).
Parameter
Description
Minimum
Maximum
ON State Voltage,
Active High
Configuration
Voltage applied to the input, with
respect to IOCOM, to guarantee an ON
state.
10.8V
26.4V
ON State Voltage,
Active Low
Configuration
Voltage applied to the input, with
respect to IOPWR, to guarantee an ON
state.
-26.4V
-10.8V
ON State Current
Current flow to guarantee an ON State
3.0 mA
12.0 mA
OFF State Voltage,
Active High
Configuration
Voltage applied to the input, with
respect to IOCOM, to guarantee an OFF
state.
-1.0V
3.0V