MTS Model FlexTest SE User Manual
Page 162
Models FlexTest® IIm/GT/SE Controller Hardware
Sending and Receiving Signals to a Model 407
FlexTest GT Controller Connections
162
Sending and Receiving Signals to a Model 407 Controller
After cabling the Model 407 Controller, you must configure it to receive and send
signals from the FlexTest GT Controller. The tables below list typical menu
settings. Refer to the Model 407 Controller Product Information Manual for
more information.
407 Configuration Menu
P
ARAMETER
S
ETTING
Eng Units
—
EOC Act
—
CYC Src
PROGRAM
SetPt R
150%/s (or highest)
Span R
300%/s (or highest)
Hyd Cnfg
—
Intlk Cnfg
MASTER
*
* Always designate one 407 in a station as a MASTER. If there are
other 407s in the same station, daisy-chain their interlocks and
designate them as DEPENDENT.
P/V Sens
—
Span Cnfg
1X
CMD Sel
EXT IN
Prog Out
—
407 Function Generator Menu
P
ARAMETER
S
ETTING
Wvform
EXTERN
Freq
—
Setpnt
—
Span
—
Preset
—