System cables
Dimensioning of the motor cables

2

l

26

EDSYPFLD EN 8.0

Please observe ...

… For cables suitable for trailing

– Cables suitable for trailing have a higher thermal loading capacity.
– Thus the above−named standards allow for higher currents.
– Therefore it may occur that a smaller cross−section is permitted for cables suitable

for trailing than for the corresponding fixedly installed cable.

… For long motor cables

– In particular in dynamic applications, depending on the cable length, you may

have to take the voltage drop on the cable into consideration.

– In these cases you must select a greater cable cross−section.

… For motors with terminal boxes

– The system cables are designed for standard cable glands.
– In order to apply other cable cross−sections, you must use extensions, reductions,

or other cable glands.