N 07

4-

37

9-

P1

K

Cygnus Operating Manual

7

(0x07)

Go to Post Deposit (Idle Ramp). Cannot be done
if in Ready, Stop, Crucible Switch, or while
crystal switching.

8

(0x08)

Go to Manual (Substrate Shutter does not
change position). Cannot be done if in Crucible
Switch or there is not a good crystal.

9

(0x09)

Set Power Level. Only allowed in Manual, Time
Power, or Non-Deposit Hold State


0 to 99.99

10

(0x0A)

Open Substrate Shutter. Only allowed if in
Manual

11

(0x0B)

Close Substrate Shutter. Only allowed if in
Manual

12

(0x0C)

Clock Hold On, Stops timer in Pre-Deposit or
Post Deposit

13

(0x0D)

Clock Hold Off, Restarts timer in Pre-Deposit or
Post Deposit after Clock Hold On.

14

(0x0E)

Continue Deposit. Go to Deposit, but don’t zero
the thickness. Cannot be done from Ready,
Stop, Crucible Switch, or while crystal switching.

15

(0x0F)

Set Averaged Rate. Only in Time Power or
Non-Deposit Hold, the estimated rate is used


0 to 999.9

16

(0x10)

Switch Crystal

17

0x11

Crystal Fail Inhibit On. Crystal Fail output always
set to FALSE, even during crystal fail.

18

0x12

Crystal Fail Inhibit Off. Crystal Fail output has
normal meaning

19

0x13

Clear Q and S counts

20

0x14

RateWatcher sampling on. Will immediately
cause the Deposit state to leave HOLD and not
return until turned off.

21

0x15

RateWatcher Sampling Off. Allows the Deposit
state to go into the RateWatcher HOLD.

Table 5-10 Remote Channel Commands (continued)

RC

Command

ID

Meaning

Action Value