Installing pdus, Recommended ups models, Installing pdus recommended ups models – HP Surestore Disk Array 12h and FC60 User Manual

Page 152

background image

152 Power Distribution Units (PDU/PDRU)

Installing PDUs

Choose PDU/PDRU locations with the following guidelines in mind:

Place PDU/PDRUs within the reach of power cords.

Place PDUs vertically whenever possible. See sample installations in

Figure 52

and

Figure 53

. Installing PDUs horizontally can interfere with accessibility to units behind

the PDU. (PDRUs must be installed vertically, as per the installation instructions.)

Place vertical PDU/PDRUs on each side of the cabinet so that the two power cords from
the enclosure’s redundant power supplies do not have to cross over replaceable
components in the middle of the product.

Thirty-amp PDRUs must be installed directly behind the disk enclosure to achieve the
highest densities in 2-meter racks. Hinged brackets allow HP’s 30-amp PDRUs (HP
E7681A and E7682A) to swing aside for servicing the disk enclosures (see

Figure 53

).

Refer to the documentation supplied with the PDU/PDRU for installation instructions.

Recommended UPS Models

The following Hewlett-Packard Power Trust models are recommended for use with the HP
SureStore E Disk Array FC60. Each UPS supplies up to 15 minutes of standby power.

Table 20

Recommended UPSs

Disk Array Configuration

UPS Product
Number

Output Power

Package

Controller enclosure and up
to two disk enclosures

A2998B

3.0 kVA (3.0 kW)

Rackmount

Controller enclosure and up
to four disk enclosures

A3589B

5.5 kVA (5.5 kW)

Rackmount

Controller enclosure and up
to six disk enclosures

A1350A

8.0 kVA (8.0 kW)

Standalone