beautypg.com

HP Surestore Disk Array 12h and FC60 User Manual

Page 148

background image

148 Site Requirements

*

In-rush current occurs for 10 to 12 milliseconds

Table 14

Total Operating and In-Rush Currents

Operating
Current
@ 110v

Operating
Current
@ 220v

In-Rush

*

Current

Power
Cords

Controller w/ 6 Disk Enclosures

41.3A

20.4A

124A

14

Controller w/ 5 Disk Enclosures

34.8A

17.2A

104A

12

Controller w/ 4 Disk Enclosures

28.3A

14.0A

84A

10

Controller w/ 3 Disk Enclosures

21.8A

10.8A

64A

8

Controller w/ 2 Disk Enclosures

15.3A

7.6

44A

6

Controller w/ 1 Disk Enclosure

8.8

4.4A

24A

4

Table 15

Controller Enclosure Electrical Requirements

Measurement

Value @ 110v

Value @ 220v

Voltage
– Range
– Frequency

100-127V
50 - 60 Hz

220-240V
50 - 60 Hz

Current
– Typical
– Maximum Operating
– Inrush

1.5A
2.3A
21.4A

0.8A
1.2A
42.9A