Power Distribution Units (PDU/PDRU) 151

Inst

alla

tion

The following tables show recommended PDU/PDRU combinations for one or more
components in a rack. Data assumes 220V AC nominal power and redundant PDU/PDRUs.
For nonredundant configurations, divide the number of recommended PDU/PDRUs by 2.

* Supports cabinet on/off switch.
** Rack height does not allow additional enclosures.

* Supports the cabinet on/off switch option.
** Rack height does not allow additional enclosures.

Table 18

Recommended PDU/PDRUs for HP Legacy Racks

Number of
Components

1.1-meter (21 U) Rack

1.6-meter (32 U) Rack

2.0-meter (41 U) Rack

1 – 4

Two 3-foot/16-amp PDUs*

or

Two 19-inch/16-amp PDUs

Two 5-foot/16-amp PDUs*

or

Two 19-inch/16-amp PDUs

5 – 8

NA**

Two 19-inch/30-amp PDRUs

9 – 10

NA**

NA**

Four 19-inch/30-amp PDRUs

Table 19

Recommended PDU/PDRUs for HP System/E Racks

Number of
Enclosures

1.25-meter (25 U) Rack

1.6-meter (33 U) Rack

2.0-meter (41 U) Rack

1 – 4

Two 19-inch/16-amp PDUs

or

Two 19-inch/30-amp PDRUs*

5 – 8

NA**

Two 19-inch/30-amp PDRUs*

9 – 11

NA**

NA**

4 19-inch/30-amp PDRUs