4. XSEL-R/S/RX/SX/RXD/SXD

4.7 Troubleshooting

1) In case it is not possible to connect the network, check the current condition on the display of

monitoring LEDs of CC-Link Board. [Refer to Section 1.10]
Check the settings of the XSEL controller and the settings of the master unit referring to the
instruction manuals of the master unit.

2) When an alarm is issued, an alarm code gets output to the panel window of the XSEL controller.

(1) Find the alarm code that you see on the window from the alarm code list shown below.

Deal with it based on the description for the alarm code in question.

(2) In case the alarm code is not found in the following list, search in the alarm contents list

contained in XSEL Controller Instruction Manual. Deal with it based on the description for the
alarm code in question.

Alarm Code

(Fieldbus related items are chosen below)

No.

Error name

Contents and Countermeasure Treatment

56A

CC-Link System Domain Use Error

It is considered that duplication is being occurred in the
settings in between CC-Link system domain and the system
inputs and outputs described below. Check the following
parameter settings. (Since some dedicated functions are to
be assigned to CC-Link system domain, it is not available to
use them optionally.)
[Refer to the following for the examples of system input and
output ports]
1) Selection of I/O port specified function
2) Zone output
3) simple contact check zone
4) Tracking Vision System Image Capturing Command

Physical Input

5) Pulse I/O board control output

678

Extended I/O Port Assignment
Parameter Error

There is an error in a parameter related to the extended I/O
port assignment.

679

Extended I/O Port Assignment
Number Overflow Error

The number of extended I/O port assignment exceeded the
specification range.

67A

Extended I/O Port Duplicated
Assignment Error

Extended I/O port assignment has duplicated.

D56

Fieldbus error
(MinACK Timeout)

An error was detected in the communication board.
Check the condition of PLC, and reboot the XSEL controller
unless there is an error. If the same error occurs again,
please contact us.

D59

Fieldbus error
(DPRAM writing and reading)

The writing and reading error was detected in the internal
memory.
XSEL Controller reboot the controller. If the same error
occurs again, please contact us.

D5A

Fieldbus error
(TOGGLE Timeout)

A communication board error was detected.
XSEL Controller reboot the controller. If the same error
occurs again, please contact us.

D5B

Fieldbus error
(Access right retry over)

A communication board error was detected.
XSEL Controller reboot the controller. If the same error
occurs again, please contact us.

[Refer to Section 4.2]

Contents and Treatment

It is considered that duplication is being occurred in the
settings in between CC-Link system area and the system
inputs and outputs described below. Check the following
I/O parameter settings. (Since some dedicated functions
are to be assigned to CC-Link system area, it is not
available to use them optionally.)
[Refer to the following for the examples of system input and
output ports]
1) Selection of I/O port specified function
2) Zone output
3) Simple contact check zone
4) Capturing command physical output of the vision system

I/F or tracking

5) Pulse I/O board control output

CC-Link System Area Use Error