2) factory-configured parameters – IAI America E-Con User Manual
Page 59
51
3. X-SEL-J/K/P/Q/JX/KX/PX/QX
(2) Factory-configured
parameters
A: X-SEL-K
ṅ-ṅ-CC1-ṅ
B: X-SEL-K
ṅ-ṅ-CC2-ṅ
C: X-SEL-K
ṅ-ṅ-CC3-ṅ
Set
value
No. Parameter
name
Input
range
A B C
Remarks
1
I/O port assignment type
0 – 20
0
0
0
0: Fixed assignment
1: Automatic assignment (Priority: slot 1
)
* The ports only in the continuous installation
range from slot 1 are assigned for safety.)
2
Standard I/O fixed assignment time:
Input port start No. (I/O 1)
-1 – 599
-1
-1
-1
0 + (multiples of 8) (Invalid for negative values)
3
Standard I/O fixed assignment time:
Output port start No. (I/O 1)
-1 – 599
-1
-1
-1
300 + (multiples of 8)
(Invalid for negative values)
4
Expansion I/O 1 fixed assignment
time: Input port start No. (I/O 2)
-1 – 599
-1
-1
032
0 + (multiples of 8) (Invalid for negative values)
(Slot next to the standard I/O)
5
Expansion I/O 1 fixed assignment
time: Output port start No. (I/O 2)
-1 – 599
-1
-1
332
300 + (multiples of 8)
(Invalid for negative values)
6
Expansion I/O 2 fixed assignment
time: Input port start No. (I/O 3)
-1 – 599
-1
016
016
0 + (multiples of 8) (Invalid for negative values)
7
Expansion I/O 2 fixed assignment
time: Output port start No. (I/O 3)
-1 – 599
-1
316
316
300 + (multiples of 8)
(Invalid for negative values)
8
Expansion I/O 3 fixed assignment
time: Input port start No. (I/O 4)
-1 – 599
0
0
0
0 + (multiples of 8) (Invalid for negative values)
9
Expansion I/O 3 fixed assignment
time: Output port start No. (I/O 4)
-1 – 599
300
300
300
300 + (multiples of 8)
(Invalid for negative values)
10 Standard I/O error monitoring
(I/O 1)
0 – 5
0
0
0
11
Expansion I/O 1 error monitoring
(I/O 2)
0 – 5
0
0
2
12 Expansion I/O 2 error monitoring
(I/O 3)
0 – 5
0
2
2
13 Expansion I/O 3 error monitoring
(I/O 4)
0 – 5
2
2
2
0: Non-monitoring
1: Monitoring
2: Monitoring (Non-monitoring of 24V I/O power
related errors)
(Main application of Ver. 0.55 or later)
3: Monitoring (Monitoring of 24V I/O power related
errors only)
(Main application of Ver. 0.55 or later)
14 Network I/F card remote: Number of
ports used for input
0 – 256
0
0
0
Multiples of 8
15 Network I/F card remote: Number of
ports used for output
0 – 256
0
0
0
Multiples of 8
(I/O 1) to (I/O 4) indicate the slot numbers.
(Note) When a standard I/O board is not used, it is not required to supply 24V DC to the I/O 24V power connector. In this case,
set the parameter No. 10 to “0.”