IAI America E-Con User Manual
Page 31

23
3. X-SEL-J/K/P/Q/JX/KX/PX/QX
(2)
Combined use of CC-Link board and I/O board
a.
The following is the setting in the case where automatic assignment allocates 256 points each for input and
output to the CC-Link board as the standard I/O ports as well as 32 points for input and 16 points for output
to the expansion I/O board IA-103-X-32 from the subsequent I/O port numbers.
The J type has the same setting.
Input port No. 256 – 287
Output port No. 556 – 571
Input port No. 000 – 255
Output port No. 300 – 555