IAI America E-Con User Manual
Page 42

34
3. X-SEL-J/K/P/Q/JX/KX/PX/QX
3.1.7 Correspondence between X-SEL I/O port number and PLC address
PLC sets the X-SEL CC-Link board as a remote device.
The number of occupied stations of the remote device varies according to the setting of the number of I/O
points on the X-SEL side.
The table below indicates the correspondence between the I/O port number and PLC address according to
the settings of I/O parameters No. 14 and No. 15. (The following is a case where the I/O parameters No. 2
and No. 3 have standard settings [defaults].)
Note: For the I/O parameters No. 14 and No. 15, set the same points according to the larger number of points.
(1)
When the number of I/O points is set to 96 or less:
Configured as one remote device. (One station occupied)
I/O parameter
No. 14 No. 15
X-SEL side DI
(Port No.)
PLC side
X-SEL side DO
(Port No.)
PLC side
16
16
000 – 015
RY
0 – F
300 – 315
RX
0 – F
32 32
016 – 031
RY
10 – 1F
316 – 331
RX
10 – 1F
48
48
032 – 047
RWw 0
332 – 347
RWr 0
64
64
048 – 063
RWw 1
348 – 363
RWr 1
80
80
064 – 079
RWw 2
364 – 379
RWr 2
96
96
080 – 095
RWw 3
380 – 395
RWr 3
* Since the shaded portions are the system areas for the remote device station on the PLC side, they
cannot be used as I/O.
(2)
When the number of I/O points is set to 112 or more and 192 or less:
Configured as two remote devices. (Two stations occupied)
I/O parameter
No. 14 No. 15
X-SEL side DI
(Port No.)
PLC side
X-SEL side DO
(Port No.)
PLC side
(16)
(16)
000 – 015
RY
0 – F
300 – 315
RX
0 – F
(32)
(32)
016 – 031
RY
10 – 1F
316 – 331
RX
10 – 1F
(48)
(48)
032 – 047
RY
20 – 2F
332 – 347
RX
20 – 2F
(64) (64)
048 – 063
RY
30 – 3F
348 – 363
RX
30 – 3F
(80)
(80)
064 – 079
RWw 0
364 – 379
RWr 0
(96)
(96)
080 – 095
RWw 1
380 – 395
RWr 1
112
112
096 – 111
RWw 2
396 – 411
RWr 2
128
128
112 – 127
RWw 3
412 – 427
RWr 3
144
144
128 – 143
RWw 4
428 – 443
RWr 4
160
160
144 – 159
RWw 5
444 – 459
RWr 5
176
176
160 – 175
RWw 6
460 – 475
RWr 6
192
192
176 – 191
RWw 7
476 – 491
RWr 7
* Since the shaded portions are the system areas for the remote device station on the PLC side, they
cannot be used as I/O.