IAI America E-Con User Manual
Page 28
20
3. X-SEL-J/K/P/Q/JX/KX/PX/QX
(3)
Factory-configured parameters of P/Q type
No. Parameter
name
Input
range
Set
value
Remarks
1
I/O port assignment type
0 – 20
1
0: Fixed assignment
1: Automatic assignment (Priority: Network I/F
module
o slot 1 (Standard I/O) -,
* The ports only in the continuous installation
range from slot 1 are assigned for safety.)
2
Standard I/O fixed assignment time:
Input port start No. (I/O 1)
-1 – 599
-1
0 + (multiples of 8) (Invalid for negative values)
3
Standard I/O fixed assignment time:
Output port start No. (I/O 1)
-1 – 599
-1
300 + (multiples of 8)
(Invalid for negative values)
4
Expansion I/O 1 fixed assignment
time: Input port start No. (I/O 2)
-1 – 599
-1
0 + (multiples of 8) (Invalid for negative values)
(Slot next to the standard I/O)
5
Expansion I/O 1 fixed assignment
time: Output port start No. (I/O 2)
-1 – 599
-1
300 + (multiples of 8)
(Invalid for negative values)
6
Expansion I/O 2 fixed assignment
time: Input port start No. (I/O 3)
-1 – 599
-1
0 + (multiples of 8) (Invalid for negative values)
7
Expansion I/O 2 fixed assignment
time: Output port start No. (I/O 3)
-1 – 599
-1
300 + (multiples of 8)
(Invalid for negative values)
8
Expansion I/O 3 fixed assignment
time: Input port start No. (I/O 4)
-1 – 599
-1
0 + (multiples of 8) (Invalid for negative values)
9
Expansion I/O 3 fixed assignment
time: Output port start No. (I/O 4)
-1 – 599
-1
300 + (multiples of 8)
(Invalid for negative values)
10 Standard I/O error monitoring (I/O 1)
0 – 5
0
11 Expansion I/O 1 error monitoring (I/O
2)
0 – 5
0
12 Expansion I/O 2 error monitoring (I/O
3)
0 – 5
0
13 Expansion I/O 3 error monitoring (I/O
4)
0 – 5
0
0: Non-monitoring
1: Monitoring
2: Monitoring (Non-monitoring of 24V I/O power
related errors)
(Main application of Ver. 0.55 or later)
3: Monitoring (Monitoring of 24V I/O power related
errors only)
(Main application of Ver. 0.55 or later)
14 Network I/F card remote:
Number of ports used for input
0 – 256
64
Multiples of 16
15 Network I/F card remote:
Number of ports used for output
0 – 256
64
Multiples of 16
16 Network I/F module fixed assignment
time: Number of ports used for input
-1-599
0
0+ (multiple of 16) (Invalid for negative values)
17 Network I/F module fixed assignment
time: Number of ports used for output
-1-599
300
300+ (multiple of 16) (Invalid for negative values)
18 Network I/F module error monitoring
0-5 1
0:
Non-monitoring
1: Monitoring
* Some exceptions included.
(I/O 1) to (I/O 4) indicate the slot numbers.