background image

4-36 PLS Functions

Resolver Mode

Backplane

PL-1746 Function Name

SLC 500

Mapping Read/

Valid Range for Data

File

Index

Write

Address

Number

Capability

Resolver Mode

M0:S.60

248

R/W*

0=Master 1=Slave

*Not while
running

Screen

MAIN SCREEN

to CONFIG MENU

to SECONDARY SETUP

to

RESOLVER MODE

RESOLVER MODE
MASTER<

Use SEL to set the opposite mode, followed by ENT to assign the new selection, or
ESC to cancel the new selection.

Description

It is sometimes necessary to connect two PL-1746 controls to a single resolver. This
function allows one PL-1746 to provide excitation to the resolver (master) and the sec-
ond PL-1746 to monitor the position of the resolver (slave).

This screen is used to select the resolver mode for PL-1746-C01 ONLY. For C02/C03/
C04 the Resolver Mode is set via DIP switch, and the screen/register is read-only.

NOTE: Setting a module to slave mode turns off the reference signal to the re-
solver. If a reference signal is not supplied by another module, the resolver posi-
tion and speed data will be random, and (in C02/C03 models) an “EX07 Resolver
not OK” message will result.

RPM Update Rate

Backplane

PL-1746 Function Name

SLC 500

Mapping Read/

Valid Range for Data

File

Index

Write

Address

Number

Capability

RPM Update Rate

M0:S.49

226

R/W

0=1/s 1=2/s 2=10/s

Screen

MAIN SCREEN

to CONFIG MENU

to SECONDARY SETUP

to

RPM UPD RATE

RPM UPDATE
RATE: 1/S<

Press the SEL key to toggle the selection.

Description

The RPM Update Rate is how often the RPM display on the Main Screen is updated.

N/A C02, C03, C04
Set via DIP switch on plug-in card