9-3 Specifications & Factory Defaults
Output Specifications
Minimum
Typical
Maximum
Operating Voltage
20 V dc
24 V dc
30 V dc
Carry Current
1.5A dc
Leakage Current
150
µ
A dc
Turn-On Time
10
µ
s
50
µ
s
Turn-Off Time
20
µ
s
50
µ
s
Input Specifications
Minimum
Typical
Maximum
Absolute Maximum Voltage
30 V dc
Pickup Voltage
9.2 V dc
11.0 V dc
Dropout Voltage
7.0 V dc
9.2 V dc
Current Draw
3.5 mA dc
20 mA dc
PL-1746-C02/C03 Module Specifications (Cont'd)
On the -C02 ALL outputs are SOURCING, on the -C03 ALL outputs are SINKING.
PL-1746-C04 Module Specifications
Electrical (The PL-1746-C04 controller is UL and UL-C listed)
I/O Power:
20-30 VDC @ 80 mA plus 150 mA per PS-6400 keypad (include power supply warming).
Backplane Power:
5VDC @ 500 mA max.
Permanent Memory:
EEPROM (no battery required).
Environment
Operating Temp:
0
°
to 55
°
C (32
°
to 131
°
F).
Storage Temp:
-40
°
to 70
°
C (-40
°
to 160
°
F).
Humidity:
95% maximum relative non-condensing.
NEMA Rating:
Keypad/Display: NEMA 4
Physical
Weight:
PLS Module: 0.5 lbs (0.2 kg). Keypad/Display: 0.5 lbs. (0.2 kg).
Mounting
Controller:
Mounts in SLC-500 chassis.
Keypad/Display:
Mounts up to 1000' from controller. Multiple keypads may be connected to one controller.
Operation
Scan Time:
Less than 1000
µ
s typical (exact time determined by programming).
For faster response, interrupt-driven versions available—consult factory.
Position Resolution:
12 bits (4096 increments).
Speed Compensation:
Programmed in 0.1 msec steps. 16 individually compensated outputs max. Updated five times
per second. Separate leading/trailing edge compensation standard.
Output Timeout:
1.0 ms time base (accuracy: +1, -0 ms).
Number of Timed Outputs:
Four maximum.
Multiple Programs:
48 programs standard.
Total Pulse Memory:
1252 pulses standard.
Pulses per Program:
512 maximum standard.
Pulses per Output:
512 maximum standard.
Maximum Speed:
3000 RPM, Note: Pulses generated with Pulse Train command are not included in pulses per
program or pulses per output counts.