8-3 Utility & Example Ladder Programs

C01 & C04 Configuration.rss (cont’d)

“Write” Configuration Information from PLC Program to PL-1746
To “Write” configuration information from the PLC program to the PL-1746, perform the following steps:

1. Ensure keyswitch is in the ‘PROG’ state on your SLC CPU.
2. Download C01 & C04 Configuration.rss PLC program into your SLC CPU.
3. Set B3/15 to ‘1’ (WRITE).
4. Turn the SLC CPU keyswtich to ‘RUN’.
5. Toggle B3/2 high (set to 1).

Once this has been accomplished, all configuration information stored in the Data Files N10-(M0-1), N11-(M0-2) and
N12-(M0-3) will be transferred from the PLC program to the configuration memory in the PL-1746.

Zero All Configuration Data
If you would like to zero all configuration information that is stored in the controller, you must go to the Data Files, enter
all zeroes into the configuration values leaving the M0 # alone, then write these values back into the controller. Refer to
the Data File shown above. In order to write a zero to that M0 register, the M0 Number must remain in the Data File, only
the ‘Data’ must be set to zero.