10 installation – Electro Cam PL-1746 Series User Manual

Page 20

background image

2-10 Installation

Termination resistors for the data and clock differential pairs are switched into the communications circuit by the S1
DIP switch. Line termination should be employed only on the rack furthest from the PLS module.

Switch

OFF

ON

3

Data Line Not Terminated

Data Line Terminated into 120W

4

Clock Line Not Terminated

Clock Line Terminated into 120W

Line Termination
Inputs
The rack has 8 inputs, and up to two racks can be daisy-chained in a given system; however, the inputs for the
second rack are ignored. Each input is optically isolated and has a green LED status indicator. The terminals are
labeled I0 through I7. All user connections to the inputs are made via a pluggable header. Each input has a single
terminal and there is one common terminal, labeled C. An input’s state is a logic one when current is flowing through
its terminal on the connector, and it’s state is a logic zero when current is not flowing. The inputs are not fused.

To source current to the inputs, wire the rack’s common terminal to the negative terminal of an
external power supply (see page 3-6).

To sink current from the inputs, wire the rack’s common terminal to the positive terminal of an
external power supply (see page 3-6).

Minimum

Typical

Maximum

Absolute Maximum Voltage

----

----

30 V dc

Pickup Voltage

9.2 V

11.0V

Dropout Voltage

7.0V

9.2V

----

Current Draw

----

3.5mA

20 mA dc

See datasheet for Phoenix 1755804 header and 1792825 plug for insulation ratings.

Digital Outputs
The rack has 16 relay slots, so the maximum of two racks allows a system total of 32 power outputs. Digital outputs
are provided by SLIMLINE solid state relays or reed relays, and thus have specifications dependent on the relays
used. All user connections to the outputs are made via pluggable headers, and plugs are included with the rack when
it is shipped from the factory. The output terminals are labeled M0A, M0B through M15A, M15B, where the number is
the output number and dc conventional current flows into the B terminal and out of the A terminal.
The maximum current rating for each module installed in the PS-4108 rack is as stated in the module's speci-
fications, OR 1.5 amps, whichever is less.

See datasheet for Phoenix 1755794 header and 1792812 plug for insulation ratings.

Analog Outputs
The rack can control up to two

analog modules in positions A0 and A1. Only one rack (the one with address 0) in a

given system can have analog outputs. Analog outputs are provided by slimline analog modules, and thus have
specifications dependent on the modules used. A pluggable header is used for wiring to the analog outputs, and a
plug is included with the rack when it is shipped from the factory. The terminals are labeled such that, for analog
output 0, conventional current flows out of the A0 terminal, through the load, and returns to the - terminal for analog
output 0. Similarly, for analog output 1, conventional current flows out of the A1 terminal, through the load, and
returns to the - terminal for analog output 1.

See datasheet for Phoenix 1755752 header and 1792773 plug for insulation ratings

Status Indicators
RUNNING

During normal operation the green

RUNNING LED (D12) is lit.

COMMUNICATIONS

When Rack-to-PLS communications are ongoing the yellow
COMMUNICATIONS LED (D11) is lit.

PS-4108-13-L16 I/O Rack Installation