beautypg.com

Password, 24 pls functions – Electro Cam PL-1746 Series User Manual

Page 69

background image

4-24 PLS Functions

Password

Backplane

PL-1746 Function Name

SLC 500

Mapping Read/

Valid Range for Data

File

Index

Write

Address

Number

Capability

Master Password

M0:S.106

340

R/W

0-9999

Setup Password

M0:S.105

338

R/W

0-9999

Operator Password

M0:S.104

336

R/W

0-9999

Screen

MAIN SCREEN

to PASSWORD

PASSWORD:****<
LEV:NONE INP:OFF

Password entry area
Keypad programming terminal input status

Current programming level (hardware or software)

Enter a password through the numeric keypad followed by ENT. As you press the
number keys, the asterisks will be replaced by dashes. If you make a mistake, press
CLR to erase the last key you pushed.

PASSWORD:--**<
LEV:NONE INP:OFF

Dashes replace asterisks as numbers are entered

PASSWORD:****<
LEV:MAS INP:OFF

Dashes change back to asterisks with ENT

Enable level shown if number matches programmed password value

Description

This screen provides an area to enter a password. It also shows the current program-
ming access level and the status of the Programming Enable terminals on the back of
the keypad.

There are three programming access levels; OPERATOR, SETUP, and MASTER. The
codes that correspond to each level are established in the ENABLE CODES screen.

If you enter a password that has been programmed through ENABLE CODES, the
keypad will function at the corresponding programming level. See ENABLE CODES for
a description of the various levels.

If either of the programming enable terminals on the back of the keypad is active when
a password is entered, the programming level will be whichever is greater.

When programming operations are completed, enter a password value of “0”, then ENT
to clear the enable level.

If a keypad is left unattended with an active password, the access code will clear after
five minutes of keypad inactivity and the keypad will revert to the “Normal Display”
mode.

There is no password for the backplane. All configuration and setpoint data is always
accessible.

Also see ENABLE CODES.