7-6 Troubleshooting
Error Messages: PL-1746-C01 Module
The module cannot be repaired in the field. If a unit fails, do not disassemble it.
Return it to the factory for replacement.
The PL-1746 major errors will fault the SLC 500 CPU. The following are the error codes displayed on the PL-1746
module and their meanings:
PLS Module Display Readout
RS Logix 500 Major Errors - Troubleshooting
EX 05 Interrupt from unused vector
S75
Call factory.
EX 06 NMI without PWRFAIL_
S76
Call factory.
EX 07 Resolver not OK
S77
Check resolver wiring.
EX 08 Backplane overflow
S78
Check ladder for too many writes to the M0 or M1 file.
EX 09 SLC interface pipe is full
S79
Call factory.
EX 0A SLC fatal error
S7A
Call factory.
EX 0B SLC access timer time-out
S7B
Call factory.
EX 0C Rack interface time-out
S7C
Check I/O rack configuration and DIP switches.
EX 0D Power supply failed
S7D
Check to see if 24VDC is present on front of module.
EX 0E PS-4108 Rack interface data error
S7E
Check I/O rack configuration and DIP switches.
EX 0F PS-4108 Rack interface time-out
S7F
Check I/O rack configuration and DIP switches.
and data error
Error Messages: PL-1746-C02/C03 Module
The module cannot be repaired in the field. If a unit fails, do not disassemble it.
Return it to the factory for replacement.
The following are the error codes displayed on the PL-1746 module. These errors will appear in the Hardware Status
Register I:S.5. To clear the error, toggle bit O:S.0/8 ON and OFF. See Input Status Register in Chapter 3, page 3-3.
PLS Module Display Readout
Troubleshooting
EX 05 Interrupt from unused vector
Call factory.
EX 06 NMI without PWRFAIL_
Call factory.
EX 07 Resolver not ok
Check resolver wiring.
EX 08 Backplane overflow
Check ladder for too many writes to the M0 or M1 file.
EX 09 SLC interface pipe is full
Call factory.
EX 0A SLC fatal error
Call factory.
EX 0B SLC access timer time-out
Call factory.
EX 0C SLC queue overflow
Call factory.
EX 0D Power supply failed
Check to see if 24VDC is present on front of module.
EX 0E System Busy
See Hardware Status/Error Register in Chapter 3, page 3-3.
EX 0F Reserved
Note: The PL-1746-C02/C03 has a green POWER LED, which lights to indicate that
the CPU is out of reset, and a yellow FAULT LED which lights if there is a PL-1746-C02
system fault.