beautypg.com

16 installation, Analog output a0 - a1 – Electro Cam PL-1746 Series User Manual

Page 26

background image

2-16 Installation

External
Power
Supply

Sinking
Device

I

0

I

1

I

2

I

3

I

4

I

5

I6

I7

C

(-)

(+)

External
Power
Supply

Sourcing
Device

I

0

I

1

I

2

I

3

I

4

I

5

I6 I7

C

(-)

(+)

PS-4108-13-L08 I/O Rack Installation

I0

Group One Input

I1

Group Two Input

I2

Group Three Input

I3

Group Four Input

I4

Group Five input

I5

Group Six Input

I6

1st Cycle Enable

I7

Output Enable

Sinking
Devices

Sourcing
Devices

• Analog output modules source the analog signal.

• No external supply is required.

• Analog output signals are isolated.

"AO"

"-"

Analog Output

A0 - A1 -

Sinking/Sourcing Defined

Sinking means that when the logic is true and the output (or input device) is ON, the output (or input device)
is providing a DC common or ground to the connected device.

Sourcing means that when the logic is true and the output (or input device) is ON, the output (or input device)
is providing a +DC voltage to the connected device.

This information is important when interfacing an Electro Cam Corp. product with another electronic device. If you are using an Electro Cam Corp. product
input to an Allen-Bradley 1746-IN16 “sinking” input card* or similar A-B device, you have to supply a +DC voltage (Electro Cam Corp.

Sourcing output)

to this card, NOT a DC common or ground. In these cases,

Sinking is what the card does with the input voltage; sinks it to common or ground.

*Other manufacturers include, but not limited to: Koyo (formerly GE Series 1, Texas Instruments, or Siemens SIMATIC PLS’s) that use descriptions
similar to Allen-Bradley.