6 ring-coupling port, 7 ring-coupling redundancy-mode, Ring-coupling port – Pilz PSSnet SHL 8T MRP User Manual
Page 305

CLI Commands: Switching
PSSnet SHL - Command Line Interface
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
5.5 Redundant Coupling
305
5.5.6 ring-coupling port
Configure the Ring Coupling's ports. Possible values are:
D
control Enter the Ring Coupling's control coupling port in outband
configurations.
D
local Enter the Ring Coupling's local coupling port.
D
partner Enter the Ring Coupling's partner coupling port in single mode
configuration.
Default
none
Format
ring-coupling port <{control|local|partner}>
Mode
Global Config
5.5.7 ring-coupling redundancy-mode
Configure the Ring Coupling's redundancy mode. Possible values are:
D
extended Slave responds to a failure in the remote ring or network.
D
normal Slave does not respond to a failure in the remote ring or network.
Default
extended
Format
ring-coupling redundancy-mode <{extended|normal}>
Mode
Global Config