Chapter 5. Programming the PLC - 139
Transmit Sequence Number Init Message
5.4.7.2. Transmit Sequence Number Init Message
The following screen depicts a SLC Typed Read - Transmit Sequence Number Init message in ladder logic. In
the ladder logic, double-click the Setup Screen in the MSG instruction.
Make the following changes:
1.
Set the Channel parameter to 1 to use the Ethernet port.
2.
Specify the file address where the transmit sequence number resides in the Data Table Address box on This
Controller panel. For more information on file addresses, see
2.4.2.1. DeviceMaster UP File Addressing
3.
Type 1 in the Size of Elements box.
4.
Specify the port-specific transmit sequence number file address for the DeviceMaster UP in the Data Table
Address box on the Target Device panel. For more information on file addresses, see
5.
Set the Routing Information File (RI) to that of your PLC program.
6.
Select the MultiHop pane. On the first line, type the IP address for the DeviceMaster UP in the To Address
box.