Configuring the DeviceMaster UP for the RSLogix 5000 Example Programs Using the Web Page
5.3.6. Configuring the DeviceMaster UP for the RSLogix 5000 Example Programs
Using the Web Page
The following procedure configures the DeviceMaster UP for the RSLogix 500 example programs. You must
perform this task before you configure and run the RSLogix 500 example program. For more information on
the Server Configuration web pages, see
Chapter 3. Embedded Configuration Pages
1.
Attach a loopback plug to the serial port.
2.
Access the Server Configuration web page, using one of these methods.
•
Open PortVision DX, right-click the DeviceMaster UP for which you want to program network
information and click Webpage.
•
Open a browser and type the IP address for the DeviceMaster UP in the Address box.
3.
Click Port n. Where n is the port number.
4.
Set the serial port settings under Serial Configuration to the following values.
5.
Set the serial port settings under Serial Packet Identification to these values.
6.
Set the serial port settings under Ethernet/IP Settings to the following values:
7.
Click Submit.
Field
Setting
Mode
RS-232
Baud
57600
Parity
none
Data Bits
8
Stop Bits
1
Flow Control
none
DTR
off
Rx Timeout Between Packets
200
Field
Setting
STX RX Detect
Set to one byte and Byte 1 to 2.
ETX Rx Detect
Set to one byte and Byte 1 to 3.
STX Tx Append
Set to one byte and Byte 1 to 2.
ETX Tx Append
Set to one byte and Byte 1 to 3.
Strip Rx STX/ETX
Select
Discard Rx Packets With Errors
Select
Field
Selection
TX Sequence Number
Checking
Select.
Rx (To PLC) Ethernet
Transfer Method
•
Set to Polling for lpbkExamplePolling.
•
Set to Write-to-Tag/File for lpbkExampleTagWrite.
•
Set to Write-to-Tag/File-Synced for lpbkExampleTagWriteSynced.
PLC IP Address
•
Leave blank for Polling.
•
Set to IP Address of PLC for Write-to-File and Write-to-File-Synced.
PLC Controller Slot
Number
Set to PLC Controller slot number which typically starts at zero. (Set to zero for
CompactLogix PLC.)
Rx (To PLC) Produced
Data Tag/File Name
•
Leave blank for Polling.
•
Set to Com1_RxData, the PLC receive filename for Write-to-Tag and Write-
to-Tag-Synced.
Reset Port
Select.
Save in Flash
Select.