DeviceMaster UP EtherNet/IP User Guide: 2000424 Rev. L

Chapter 5. Programming the PLC - 107

Configuring the DeviceMaster UP for the RSLogix 5000 Example Programs Using the Web Page

5.3.6. Configuring the DeviceMaster UP for the RSLogix 5000 Example Programs

Using the Web Page

The following procedure configures the DeviceMaster UP for the RSLogix 500 example programs. You must
perform this task before you configure and run the RSLogix 500 example program. For more information on
the Server Configuration web pages, see

Chapter 3. Embedded Configuration Pages

on Page 65.

1.

Attach a loopback plug to the serial port.

2.

Access the Server Configuration web page, using one of these methods.

Open PortVision DX, right-click the DeviceMaster UP for which you want to program network
information and click Webpage.

Open a browser and type the IP address for the DeviceMaster UP in the Address box.

3.

Click Port n. Where n is the port number.

4.

Set the serial port settings under Serial Configuration to the following values.

5.

Set the serial port settings under Serial Packet Identification to these values.

6.

Set the serial port settings under Ethernet/IP Settings to the following values:

7.

Click Submit.

Field

Setting

Mode

RS-232

Baud

57600

Parity

none

Data Bits

8

Stop Bits

1

Flow Control

none

DTR

off

Rx Timeout Between Packets

200

Field

Setting

STX RX Detect

Set to one byte and Byte 1 to 2.

ETX Rx Detect

Set to one byte and Byte 1 to 3.

STX Tx Append

Set to one byte and Byte 1 to 2.

ETX Tx Append

Set to one byte and Byte 1 to 3.

Strip Rx STX/ETX

Select

Discard Rx Packets With Errors

Select

Field

Selection

TX Sequence Number
Checking

Select.

Rx (To PLC) Ethernet
Transfer Method

Set to Polling for lpbkExamplePolling.

Set to Write-to-Tag/File for lpbkExampleTagWrite.

Set to Write-to-Tag/File-Synced for lpbkExampleTagWriteSynced.

PLC IP Address

Leave blank for Polling.

Set to IP Address of PLC for Write-to-File and Write-to-File-Synced.

PLC Controller Slot
Number

Set to PLC Controller slot number which typically starts at zero. (Set to zero for
CompactLogix PLC.)

Rx (To PLC) Produced
Data Tag/File Name

Leave blank for Polling.

Set to Com1_RxData, the PLC receive filename for Write-to-Tag and Write-
to-Tag-Synced.

Reset Port

Select.

Save in Flash

Select.