Chapter 5. Programming the PLC

DeviceMaster UP EtherNet/IP User Guide: 2000424 Rev. L

Setting up Processor and Ethernet (Channel 1)

5.

Double-click Processor Status, and select the
Chan 1 tab on the Data File S2 -- STATUS dialog.

6.

Make the following recommended changes.

a.

Select the DH485 Gateway Disable Bit S:34/0
option.

b.

Clear the DF1 Gateway Enable BIT S:34/5
option.

c.

Select the Comms Servicing Sel S:2/15 option.

d.

Select the Msg Servicing Sel S:33/7 option.
(You must enable this option if you want to
run EtherNet/IP.)

7.

Optionally, double-click Channel Configuration
and type a value (between 0 and 256) in the
Diagnostic File box for an integer diagnostic file. You can use the diagnostic file to help solve any network-
related problems.