beautypg.com

Ethernet/ip application setup – Comtrol UP DeviceMaster User Guide User Manual

Page 11

background image

DeviceMaster UP Modbus/TCP User Guide: 2000447 Rev. I

Chapter 1. Introduction - 11

EtherNet/IP Application Setup

1.5. EtherNet/IP Application Setup

Before you can configure the EtherNet/IP firmware on the DeviceMaster UP, you must have previously
performed the following steps:

Install the hardware

Install PortVision DX

If necessary, upload the EtherNet/IP firmware using PortVision DX

Note: Models that have EtherNet/IP loaded on the DeviceMaster UP are identified in PortVision DX and

the DeviceMaster UP is labeled accordingly.

Configure the DeviceMaster UP IP address using PortVision DX

Note: If necessary, refer to the

DeviceMaster UP Hardware Installation and Configuration Guide

for the

above procedures.

Use the following steps to complete the DeviceMaster UP configuration for EtherNet/IP.

1.

Select the appropriate programming procedure for the following interfaces:

2.

Connect your serial device or devices and make sure all Ethernet devices are attached to the same
Ethernet subnet. If necessary, refer to the

DeviceMaster UP Hardware Installation and Configuration

Guide

.

Interfaces

Programming Procedure

ControlLogix
PLC

Program the PLC. See the instructions in

ControlLogix PLC

Programming Example Instructions

on Page 103.

(Optional) Access the DeviceMaster UP Server Configuration page to
configure the serial/socket port settings, if you did not configure the
serial/socket port setting in the PLC program. See the DeviceMaster UP
Interface Configuration Guide
for procedures and reference

Embedded

Configuration Pages

on Page 65, if necessary.

SLC or
MicroLogix PLC

Program the SLC or MicroLogix PLC, see the instructions in

SLC or

MicroLogix PLC Programming Example Instructions

on Page 116.

Access the DeviceMaster UP Server Configuration page to configure the
serial/socket port settings. See the DeviceMaster UP Interface
Configuration Guide
for procedures and reference

Embedded

Configuration Pages

on Page 65, if necessary.

PLC-5 PLC

Program the PLC-5 PLC, see the instructions in

PLC-5 PLC

Programming Example Instructions

on Page 143.

Access the DeviceMaster UP Server Configuration page to configure the
serial/socket port settings. See the DeviceMaster UP Interface
Configuration Guide
for procedures and reference

Embedded

Configuration Pages

on Page 65, if necessary.