Cable categories for kinetix 2000 systems – Rockwell Automation 2093-xxxx Kinetix 2000 Multi-axis Servo Drive User Manual User Manual
Page 34

Publication 2093-UM001A-EN-P — March 2007
34
Planning the Kinetix 2000 Drive System Installation
Observe the following guidelines when installing a 1756-MxxSE SERCOS or
other Logix interface modules:
• The clean zone (C) is beneath the less noisy modules, such as I/O,
encoder, registration (grey wireway).
• The dirty zone (D) is above and below the power supply and noisy
modules (black wireway).
• The SERCOS fiber-optic cables are immune to electrical noise.
Establishing Noise Zones (ControlLogix)
(1)
Segregate VD wiring from D and C wiring, or use shielded cable (shield bonded to both panel at both ends)
which then becomes category D.
Cable Categories for Kinetix 2000 Systems
The table below indicates the zoning requirements of cables connecting to the
Kinetix 2000 drive components.
Integrated Axis Module (Converter Side)
D
D
C
VD
D
Dirty Wireway
Clean Wireway
Route dirty wireways directly above the ControlLogix rack
(shielded by the ControlLogix chassis)
Very-dirty
filter/power supply
connections
segregated (not in
Dirty I/O
(24V dc I/O, AC I/O)
Clean I/O
(Analog, Encoder
Registration)
Spare Slot(s)
EMC
Filter
(1)
Wire/Cable
Connector
Zone
Method
Very
Dirty
Dirty
Clean
Ferrite
Sleeve
Shielded
Cable
CTRL 1 and 2
CPD
X
DC-/DC+ (unshielded cable)
IPD
X
X
L1, L2, L3 (shielded cable)
X
X
L1, L2, L3 (unshielded cable)
X
CONT EN- and CONT EN+ (M1 contactor)
CED
X
DPI
DPI
X
X