Shunt Module Power Specifications
The table below lists the power specifications for the 2093-ASP06
Shunt Module (SM).
SM Power Specifications
Circuit Breaker/Fuse Specifications
While circuit breakers offer some convenience, there are limitations for their
use. Circuit breakers do not handle high current inrush as well as fuses. A
Kinetix 2000 system needs to be protected by a device having a short circuit
interrupt current rating of the service capacity provided or a maximum of
100,000 A.
If an upstream circuit protection device is rated for the overload current and
short circuit rating, a supplementary circuit protection device (such as the 1492
product) can be used as the only Kinetix 2000 branch-circuit protection
device. The upstream fully rated device let-through must be less than or equal
to the 10 kA interrupt rating of the 1492 circuit protection device.
The wiring interconnection in the figures below provide examples of the
needed protection and follows UL and NEC codes. Full compliance is
dependent on final wiring design and installation.
Circuit Protection under NEC 1999 110-10 (preferred fully rated devices)
Kinetix 2000 Drives
Shunt Module
Catalog Number
Specifications
Fuse
Replacement
Drive
Voltage
V ac
Resistance
Ω
Peak
Power
kW
Peak
Current
A
Continuous
Power
W
Capacitance
μF
2093-AC05-MP1
2093-ASP06
(1)
230 15.0 10.9 27.0 50
164
N/A (no internal
fuse)
2093-AC05-MP2
2093-AC05-MP5
(1)
1Contact your Allen-Bradley sales representative for availability of external shunt modules.
Required Protection
under 110-10 of
NEC 1999
Preferred Fully
Rated Breakers
Distribution
Blocks
Fully Rated
Fused
Disconnect
Fully Rated
Breaker
Drive
Drive
Drive
Fully Rated
Fused
Disconnect
Fully Rated
Breaker
Breakers Selected
for Device Protection
Fully Rated Short Circuit
Interrupt Capability
Required Protection
under 110-10 of
NEC 1999
Preferred Fully
Rated Breakers
Fully Rated
Fused
Disconnect
Fully Rated
Breaker
Breakers Selected
for Device Protection
Fully Rated Short Circuit
Interrupt Capability