Specifications and Dimensions
Circuit Protection under NEC 1999 110-10 (allowed but no longer preferred)
Use class CC, J, L, or R fuses, with current rating as indicated in the table
below. The following fuse examples and Allen-Bradley circuit breakers are
recommended for use with integrated axis modules (2093-AC05-MPx) when
the Line Interface Module (LIM) is not used.
Main and Control Input Power Fuse Specifications
Required Protection
under 110-10 of
NEC 1999
Allowed But
No Longer Preferred
Distribution
Blocks
Traditional
Current Limit
Fused
Disconnect or
Breaker
Rated for
Short Circuit
Available
Limiting to
Short Circuit
Rating of Down
Stream Breaker
Breakers Selected
for Device Protection
With Limited Short
Circuit Interrupt
Capability
Drive
Drive
Drive
Required Protection
under 110-10 of
NEC 1999
Allowed But
No Longer Preferred
Traditional
Current Limit
Fused
Disconnect or
Breaker
Rated for
Short Circuit
Available
Limiting to
Short Circuit
Rating of Down
Stream Breaker
Breakers Selected
for Device Protection
With Limited Short
Circuit Interrupt
Capability
Distribution
Blocks
IMPORTANT
Line interface modules (2094-ALxxS and 2094-XL75S-Cx) provide
branch circuit protection to the IAM.
Line interface module 2094-AL09 contains a supplementary protection
device, 1492-CB (UL 508), and therefore class CC or J fuses with 5kA
SCCR must be used on the line side.
Follow all applicable NEC and local codes.
Catalog Number
Main Input Power
Control Input Power
Main Input
Fuse
Circuit Breaker
1492 Series
(1)
Fuse
(2)
2093-AC05-MP1
170...264V ac
three-phase
KTK-R-20 (20A)
1492-CB3H300
140M-F8E-C16
FNQ-R-10 (10A)
or
KTK-R-5 (5A)
1492-CB2H060
2093-AC05-MP2
2093-AC05-MP5
2093-AC05-MP1
170...264V ac
single-phase
N/A
2093-AC05-MP2
2093-AC05-MP5
(1)
When using Bulletin 1492 or 140M circuit protection devices, the maximum short circuit current available from the source is limited to 5000 A.
(2)
Fuse selection for control power is appropriate for an eight-axis system with the specified IAM.
ATTENTION
Bulletin 1492 and 140M circuit breakers should not be used on the
output of an ac drive as an isolating disconnect switch or motor
overload device. These devices are designed to operate on sine wave
voltage and the drive’s PWM waveform does not permit proper
operation. As a result, damage will occur to the device.